Kent, United Kingdom
Coldharbour Solar
Annual thermography for the asset owner. Twenty-three anomalies, including a full string offline since July.
56
ha
Area covered
46
min
Flight time
23
flagged
Anomalies found
71
°C
Hottest reading
Findings
String 22-B fully offline: whole string reads 9 K warmer than its neighbours
Seven modules with diode faults in sub-array 4
Two connectors at 71.4 °C on the main DC run
Debrief
The report was required to IEC TS 62446-3 classes, so every contact carries its anomaly class, delta-T and irradiance at capture.
The offline string had been missed by monitoring because its inverter averaged it against a healthy partner.
Twenty-three findings, each with a photo a contractor can find on site. That is what the owner pays for.
Priya Shah, asset engineer